Profibus master port – ProSoft Technology PTQ-PDPMV1 User Manual
Page 280

Reference
PTQ-PDPMV1 ♦ Quantum Platform
User Manual
PROFIBUS DP Master Network Interface Module for Quantum
Page 280 of 306
ProSoft Technology, Inc.
August 12, 2014
9.5
PROFIBUS Master Port
The following diagram has been imported from the PROFIBUS Master
documentation. Note that the signals to reference are the D-Sub signals in the
table.
9.5.1 Constructing a Bus Cable for PROFIBUS DP
The bus cable for connecting PROFIBUS DP devices must be constructed by the
user. A special PROFIBUS cable (twisted pair) is required here. This standard
cable is available from various manufacturers and is a Belden part number
3079A.
To construct the cable
1 Cut the cable to the required length.
2 Prepare the cable ends as shown in the illustration (dimensions in mm):
J PVC jacket
S Braided shielding
3 Remove the PVC jacket J to the indicated length.