ProSoft Technology PTQ-PDPMV1 User Manual
Page 167

PTQ-PDPMV1 ♦ Quantum Platform
Mailbox Messaging
PROFIBUS DP Master Network Interface Module for Quantum
User Manual
ProSoft Technology, Inc.
Page 167 of 306
August 12, 2014
Command and Response Layout: Acyclic Read
Command
Response
Message ID
(ID)
(ID)
Message information
0240h
0200h
Command
2000h
2000h
Acyclic Read
Data size
0000h
(Size of data)
Number of data bytes (n)
Frame count
0100h
0100h
Frame number
0100h
0100h
Offset high
0000h
0000h
Offset low
0000h
0000h
Extended word 1
Slot
Slave Addr.
Slot
Slave Addr.
Extended word 2
Length
Index
Length
Index
Extended word 3
-
-
Extended word 4
-
-
Extended word 5
-
Error
Decode
Extended word 6
-
Error Code 2 Error Code 1
Extended word 7
-
Extended Fault information
Extended word 8
-
Fault Information
Data 1
Response Data byte 1
Data 2
Response Data byte 1
Data 3
Response Data byte 1
...
...
Data n
Response Data byte 1
Message Information
Refer to Message Information (page 180).
Slave Address
Station address of the slave responder.
Slot Number and Slot Index
Used in the slave to address the desired data block.
Length
This parameter specifies the number of bytes of the data block that have to be
read. If the server data block length is less than requested, the length of the
response will be the actual length of the data block. If the server data block is
greater or equal, the response will contain the same amount of data.
The slave may answer with an error response if data access is not allowed.