PTQ-PDPMV1 ♦ Quantum Platform

Mailbox Messaging

PROFIBUS DP Master Network Interface Module for Quantum

User Manual

ProSoft Technology, Inc.

Page 167 of 306

August 12, 2014

Command and Response Layout: Acyclic Read

Command

Response

Message ID

(ID)

(ID)

Message information

0240h

0200h

Command

2000h

2000h

Acyclic Read

Data size

0000h

(Size of data)

Number of data bytes (n)

Frame count

0100h

0100h

Frame number

0100h

0100h

Offset high

0000h

0000h

Offset low

0000h

0000h

Extended word 1

Slot

Slave Addr.

Slot

Slave Addr.

Extended word 2

Length

Index

Length

Index

Extended word 3

-

-

Extended word 4

-

-

Extended word 5

-

Error

Decode

Extended word 6

-

Error Code 2 Error Code 1

Extended word 7

-

Extended Fault information

Extended word 8

-

Fault Information

Data 1

Response Data byte 1

Data 2

Response Data byte 1

Data 3

Response Data byte 1

...

...

Data n

Response Data byte 1

Message Information
Refer to Message Information (page 180).

Slave Address
Station address of the slave responder.

Slot Number and Slot Index
Used in the slave to address the desired data block.

Length
This parameter specifies the number of bytes of the data block that have to be
read. If the server data block length is less than requested, the length of the
response will be the actual length of the data block. If the server data block is
greater or equal, the response will contain the same amount of data.

The slave may answer with an error response if data access is not allowed.