Profibus master indicators – ProSoft Technology PTQ-PDPMV1 User Manual

Page 229

Advertising
background image

PTQ-PDPMV1 ♦ Quantum Platform

Diagnostics and Troubleshooting

PROFIBUS DP Master Network Interface Module for Quantum

User Manual

ProSoft Technology, Inc.

Page 229 of 306

August 12, 2014

8.4

PROFIBUS Master Indicators

LED

State

Description

MSTR

STAT

GREEN

OPERATE mode

GREEN-Flashing CLEAR mode
RED

STOP mode

OFF

Offfline

DBASE
STAT

GREEN

Database OK

GREEN-Flashing Database download in progress
RED

Invalid database

OFF

No databases have been downloaded

COM STAT GREEN

Data exchange with all configured slaves

GREEN-Flashing Data exchange with at least one of the configured slaves
RED

Bus control error (possible bus short circuit or configuration error)

OFF

No data exchange with any configured slave

TKN HLD

GREEN

The module has the token

OFF

The module does not have the token

ALL LEDs

RED

Fatal error

OFF

HSBY processor is stopped and Master is held in reset state (inactive)
The module is not in the configured slot