Functional Overview

HART Master with Analog I/O

Driver Manual

ProSoft Technology, Inc.

Page 17 of 104

October 13, 2011

2.2

Functional Specifications - HART Analog

The HART Analog Protocol exists in 4 and 8 channel implementations. This driver can be

configured on an individual channel basis to operate as a HART Master Station and

supports all the available HART commands including Universal, Common Practice and

Device Specific Commands. Each HART channel is independently configured to interface

with the internal database in the module.
The auto-poll mode allows the module to automatically collect data from each HART

instrument on the channel and store the data in the module’s database without the use of

user commands. The module automatically generates HART commands 0, 3, 13, 14 and

15.

General Parameters

Internal Database

4000 registers (words) available

Communication parameters

Number of HART Preambles: 2 to 50
Enable Handheld: Y or N

Primary Master: Y or N

Configurable Parameters per Channel Auto-Poll Enable

Short / Long Address Retries

Retries After Error
Poll Time After Error

Number of Commands

Slave List Error Pointer

HART Driver

Command List

Up to 100 command per channel, each fully configurable
for function, slave address, register to/from addressing and

word count for Floating Point or Integer Data

Status Data

Error codes returned by the HART protocol available on an
individual command basis. In addition, a slave status list is

maintained per active channel.

Polling of command list

User configurable polling of commands, including disabled,
continuous, on change of data (write only) and dynamically

user or automatic enabled.

Isolated HART Analog Input Specifications

Input Range

Current: 4 to 20mA with HART

Resolution

16bits

Input Filter

First Order Sync: 10 Hz

Current Input Resistance

247.6 ohms +/- 1%

Open circuit detection time

1/2 second maximum

Over current

+/-40mA continuous, maximum

Common Mode Noise Rejection

105dB

Calibrated Accuracy @ 25°C

4 to 20 mA: 0.05% of reading

Input Isolation Voltage

2500 V RMS per UL 1577, transformer isolated

24V DC Isolation Voltage

1500 VDC

HART

®

is a registered trademark of the HART Communication Foundation