ProSoft Technology 5228-DFNT-HART User Manual

Page 90

Advertising
background image

Reference

ProLinx-HART ♦ ProLinx Gateway

Driver Manual

HART Master with Analog I/O

Page 90 of 104

ProSoft Technology, Inc.

October 13, 2011

4.4

ProLinx 5108 / 5208 HART Field Connections

HART field instruments are divided into four types; A through D, depending on power

requirements and whether the device sinks or sources a bias or operating current from

the network. The following table defines the categories:

Type

Description

A

Type A field instruments sink direct current from the network and receive operating
power from the network.

B

Type B field instruments sink direct current from the network but receive no operating
power from the network.

C

Type C field instruments source direct current to the network and receive no operating
power from the network.

D

Type D field instruments neither source nor sink direct current from the network, nor
receive operating power from the network.


On a given network channel, Type A, B, and D devices may be combined. Type C and D

devices may also be combined. Type A or B field instruments should not be combined

with Type C devices.

4.4.1 Connections for HART Analog Point-to-Point Devices

The ProLinx 5108/5208 HART Analog interface module provides an isolated 24 Vdc

power supply output which may be used as a Network Power Supply. It is sized for

powering one HART Analog transmitter for each of the four HART Analog channels. This

internal isolated power supply can supply 24 Vdc @125 mA maximum, which is sufficient

to supply power to four HART analog transmitters, each connected in a point-to-point

fashion. Since each HART Analog channel is independent and completely isolated, any

mixture of loop powered and self powered transmitters may be accommodated. External

loop power, internal loop power, or both may be used to power any HART Analog

channel.

Important: The 5108/5208 HART Analog module may not be used for multi-drop

applications. Only one HART transmitter per channel is allowed.

4.4.2 Network Power Supply Requirements

Type

Network Power Supply

A

Required

B

Required

C

Must not be used.

D

Not required, but may be used.

Note: The ProSoft 5108/5208 HART interface may be used with any HART field

device transmitter.

Advertising
This manual is related to the following products: