ProSoft Technology 5228-DFNT-HART User Manual

Page 84

Advertising
background image

Reference

ProLinx-HART ♦ ProLinx Gateway

Driver Manual

HART Master with Analog I/O

Page 84 of 104

ProSoft Technology, Inc.

October 13, 2011

COMMAND 110 - Read All Dynamic Variables

Description

This command gets all dynamic Variables.

Write Parameters

NONE

Floating Point Data Returned

Word

High Byte

Low Byte

0

Primary Variable

1
2

Second Variable

3
4

Third Variable

5
6

Fourth Variable

7

Integer Data Returned

Word

High Byte

Low Byte

0

STATUS WORD

1

Primary Variable Units Code

Second Variable Units Code

2

Third Variable Units Code

Fourth Variable Units Code