HART Protocol Configuration

ProLinx-HART ♦ ProLinx Gateway

Driver Manual

HART Master with Analog I/O

Page 36 of 104

ProSoft Technology, Inc.

October 13, 2011

3.3.19 Fixed Data

Up to 250 HEX values separated by space
This parameter is a string of HEX values to be sent with the HART command. There

should be at least the number of bytes specified in the "Byte Count" parameter. The

bytes should be written in hexadecimal format and separated by a space. This data will

be sent if the Parameter "Write DB Address" is "-1" and "Byte Count" is greater than "0",

and it will be sent in the same order that they are written.