ProSoft Technology 5228-DFNT-HART User Manual

Page 86

Advertising
background image

Reference

ProLinx-HART ♦ ProLinx Gateway

Driver Manual

HART Master with Analog I/O

Page 86 of 104

ProSoft Technology, Inc.

October 13, 2011

Status Register

Name

Description

10701

Comm State

Channel 0 communication state machine value (used

for debugging)
0 Startup
1 Idle
2 Transmit Pending
3 Transmit
4 Receive
5 Post Transmit
6 Idle, Waiting

10702

Device Status (bit

mapped)

Each bit in this word corresponds to a slave address on
the network starting at bit 1 for slave address 1. Bit 0 is

not used. If the bit is set, the slave is in error. If the bit

is clear (0), the slave is not in error.

10703

Device Poll List (bit

mapped)

Each bit in this word corresponds to a slave address on
the network starting at bit 1 for slave address 1. Bit 0 is

not used. If the bit is set, the slave is in the poll list. If

the bit is clear (0), the slave is not in the poll list.

10704

Device With Long

Address (bit map)

Each bit in this word corresponds to a slave address on
the network starting at bit 1 for slave address 1. Bit 0 is

not used. If the bit is set, the slave uses the long
address. If the bit is clear (0), the slave does not use

the long address.

10705

Current Command

This field contains the index of the current command to

execute.

10706

Command Request

Count

This field contains the total number of request

messages issued on the port.

10707

Command Response

Count

This field contains the total number of response

messages received from devices on the network.

10708

Configuration Error

Word

Configuration error word (see HART Configuration

Error Word (page 89))

10709

Current Error Code

Current error code for port

10710

Last Error Code

Last error code reported for port

10711

No Valid Data


10799

Status Register

Description

10800

Command List Status and Errors


10899