Reference

ProLinx-HART ♦ ProLinx Gateway

Driver Manual

HART Master with Analog I/O

Page 76 of 104

ProSoft Technology, Inc.

October 13, 2011

COMMAND 54 - Read Transmitter Variable Information

Description

This command gets information about any selected transmitter variable sensor.

Write Parameters

Word

High Byte

Low Byte

0

Transmitter Variable Code

Transmitter Variable Code

Floating Point Data Returned

Word

High Byte

Low Byte

0

Transmitter Variable Upper Limit

1
2

Transmitter Variable Lower Limit

3
4

Transmitter Variable Damping Value (Sec)

5

Integer Data Returned

Word

High Byte

Low Byte

0

STATUS WORD

1

Transmitter Variable Code

Sensor Serial Number 0

1

Sensor Serial Number 1

Sensor Serial Number 2

2

Unit Code for Limits

0