ProSoft Technology 5228-DFNT-HART User Manual

Page 88

Advertising
background image

Reference

ProLinx-HART ♦ ProLinx Gateway

Driver Manual

HART Master with Analog I/O

Page 88 of 104

ProSoft Technology, Inc.

October 13, 2011

Protocol Error Codes

These are error codes that are part of the HART protocol. The standard HART error

codes are shown in the following tables:

Error Code Word

First Byte

Second Byte

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

Bit 7 of First Byte = 1
COMMUNICATION ERROR

First Byte
Bit 6

Parity Error

Bit 5

Overrun Error

Bit 4

Framing Error

Bit 3

Checksum Error

Bit 2

Reserved

Bit 1

Rx Buffer Overflow

Bit 0

Undefined

Second Byte
Bit 0 To Bit 7

All 0

Bit 7 of First Byte = 0
Command Error

First Byte
Bits 6 To 0 (not Bit-mapped):
0

No Error

1

Undefined

2

Invalid Selection

3

Passed Parameter Too Large

4

Passed Parameter Too Small

5

Too Few Data Bytes Received

6

Transmitter-specific Command Error

7

In Write-protect Mode

8 to 15

Command Specific Errors (see Below)

16

Access Restricted

32

Device Is Busy

64

Command Not Implemented

Second Byte
Bit 7

Device Malfunction

Bit 6

Configuration Changed

Bit 5

Cold Start

Bit 4

Unused

Bit 3

Output Current Fixed

Advertising
This manual is related to the following products: