Reference

HART Master with Analog I/O

Driver Manual

ProSoft Technology, Inc.

Page 85 of 104

October 13, 2011

4.3

Error/Status Data

The module error/status data areas are discussed in this section. The module contains

three areas related to this data. The user defines the location of these data sets in the

virtual database of the module. The error/status data contains module data, the six

command error list data sets contain the errors associated with each respective

command list and the four slave status list tables contain the communication status of

each port’s slave devices.

4.3.1 Viewing Error and Status Data

The word addresses in the following topics are virtual addresses. To view the contents of

these registers, use the Data Map section (page 37) of the module configuration file to

map these values into the 4000-word database or use the Diagnostics menus in ProSoft
Configuration Builder (PCB)
. Refer to the ProLinx Reference Guide for detailed
information on viewing error and status registers.

4.3.2 Status Data Mapping Addresses (HART Channels 0 through 7)

The following table lists the register address ranges for HART Channels 0 through 7. The

status values are listed in the same order for every channel. The first eleven (11)

registers in each range are used to hold general channel status data. The last 100

registers in each range are used to hold the Command Status/Error List for that channel.

Port

Address Range

0

10700 to 10899

1

10900 to 11099

2

11100 to 11299

3

11300 to 11499

4

11500 to 11699

5

11700 to 11899

6

11900 to 12099

7

12100 to 12299

HART Channel 0 Status Data Map

This table lists the status register addresses and status descriptions for HART Channel 0.

Status values are listed in the same order for all installed HART channels (four or eight.)

Address ranges for HART Channels 0 through 7 are listed in Status Data Mapping

Addresses (page 85).

Status Register

Name

Description

10700

State

Channel 0 state machine value (used for debugging)
0 Polling
1 Config
2 Data Poll
3 User Poll
4 Wait Unique ID

Advertising