ProSoft Technology 5228-DFNT-HART User Manual

Page 45

Advertising
background image

ProLinx-HART ♦ ProLinx Gateway

Reference

HART Master with Analog I/O

Driver Manual

ProSoft Technology, Inc.

Page 45 of 104

October 13, 2011

COMMAND 03 - Read Dynamic Variables

Description

This command gets the current and four (predefined) dynamic Variables.

Write Parameters

NONE

Floating Point Data Returned

Word

High Byte

Low Byte

0

Current (mA)

1
2

Primary Variable

3
4

Second Variable

5
6

Third Variable

7
8

Fourth Variable

9

Integer Data Returned

Word

High Byte

Low Byte

0

STATUS WORD

1

Primary Variable Units Code

Second Variable Units Code

2

Third Variable Units Code

Fourth Variable Units Code