ProSoft Technology 5228-DFNT-HART User Manual

Page 73

Advertising
background image

ProLinx-HART ♦ ProLinx Gateway

Reference

HART Master with Analog I/O

Driver Manual

ProSoft Technology, Inc.

Page 73 of 104

October 13, 2011

COMMAND 51 - Write Dynamic Variable Assignments

Description

This command sets the assignment of the Dynamic Variables returned with command 3.

Write Parameters

Word

High Byte

Low Byte

0

Transmitter Variable Code For Primary

Variable

Transmitter Variable Code For Second

Variable

1

Transmitter Variable Code For Third

Variable

Transmitter Variable Code For Fourth

Variable

Floating Point Data Returned

NONE

Integer Data Returned

Word

High Byte

Low Byte

0

STATUS WORD

1

Transmitter Variable Code For Primary

Variable

Transmitter Variable Code For Second

Variable

2

Transmitter Variable Code For Third

Variable

Transmitter Variable Code For Fourth

Variable

Advertising