ProLinx-HART ♦ ProLinx Gateway

Reference

HART Master with Analog I/O

Driver Manual

ProSoft Technology, Inc.

Page 89 of 104

October 13, 2011

Bit 7 of First Byte = 0
Command Error

Bit 2

Analog Output Saturated

Bit 1

Variable (not Primary) Out Of Limits

Bit 0

Primary Variable Out of Limits

Command Specific Errors

8

Update Failed
Update In Progress
Set to Nearest Possible Value

9

Applied Process Too High
Lower Range Value Too High
Not in Fixed Current Mode

10

Applied Process Too Low
Lower Range Value Too Low
Multi-drop Not Supported

11

In Multi-drop Mode
Invalid Transmitter Variable Code
Upper Range Value Too High

12

Invalid Unit Code
Upper Range Value Too Low

13

Both Range Values Out of Limits

14

Pushed Upper Range Value Over Limit
Span Too Small

HART Configuration Error Word

Bit

Code

Description

0

0x0001

Enabled not set to Y or N

1

0x0002

Enable Handheld not set to Y or N

2

0x0004

Primary Master not set to Y or N

3

0x0008

Invalid Preambles (1 to 50)

4

0x0010

Invalid Short Address Retries (0 to 50)

5

0x0020

Invalid Long Address Retries (0 to 50)

6

0x0040

Invalid Retries After Error (0 to 50)

7

0x0080

Invalid Poll Time After Error (0 to 10000)

8

0x0100

Invalid DB Address Status

9

0x0200

Invalid Command Count

10

0x0400

Memory Error in allocating commands

11

0x0800

Memory Error in allocating command fixed data

12

0x1000

Memory Error in allocating TX/RX buffers

13

0x2000

HART Board not found

14

0x4000

Cannot initialize HART channel

15

0x8000

reserved