The passive tap has two BNC connectors for connection to the coaxial
cables and terminating loads.

The network coaxial cable must be terminated with 75 ohm terminating
loads attached to the taps at the physical ends of the network. There
should be two and only two terminators on the network.

The DCS network cable can be RG-59/U or RG-11/U.

Ethernet Cabling

AN-X has a standard RJ-45 connector for connecting to Ethernet.

If you are connecting AN-X to an existing network through a router or
switch, use a standard Ethernet cable.

If you are connecting a computer or PLC directly to an AN-X, use a
crossover cable.

Software Installation

You must uninstall any previous version of the software before you can
install a new version. Use the Windows Control Panel Add and Remove
Programs to remove the old version.

Insert the CD supplied with the AN-X module and run the program
setup.exe on the CD.