AN-X-DCSNet2 Page

27

Input Only Connection

The AN-X-DCSNET2 supports one input only connection from a
ControlLogix processor. The ControlLogix processor will be able to
read the same input data as the ControlLogix processor with the
exclusive owner connection to the AN-X-DCSNET2.

The data received will depend on the mappings in the AN-X-DCSNET2.

To configure the input only connection to the AN-X-DCSNET2 in
RSLogix 5000:

1. Right click on the ControlLogix Ethernet module that will be

communicating with the AN-X and select Add Module. Add a
1756-ENBT/A module. Set the Major Rev to 1.

Set the Slot to 16. Set the chassis size to 17.

Set the Comm Format to None.

Set the IP address to match the AN-X module.

Set Electronic Keying to Disable Keying.

2. Add Generic modules for each required connection