23

2. Map DCS data to the scheduled data and save the mappings as a

comma separated variable (CSV) file

3. Send the configuration file to AN-X

Requirements

• RSLogix 5000 version 12 or above

• ControlLogix processor with firmware version 12 or above

• 100 Mbit Ethernet network and ENBT modules. We strongly

recommend using Ethernet switches rather than hubs

Reference

Allen-Bradley publication EtherNet/IP Media Planning and Installation
Manual

, publication ENET-IN001A-EN-P

Configuring AN-X in RSLogix 5000

The AN-X-DCSnet2 emulates a 17-slot 1756 chassis with an ENBT/A in
slot 16 and generic modules in slots 0 to 15.

Exclusive Owner Connection

To configure the AN-X-DCSnet2 in RSLogix 5000:

1. Right click on the ControlLogix Ethernet bridge module that will be

communicating with the AN-X and select Add Module. Add a
1756-ENBT/A module. Set the Major Rev to 1.