1.1

System Electrical Characteristics

Table 1-3: UPS Characteristics System Ratings.

Table 1-4: Transformer Module Characteristics Ratings.

CAUTION

Power Module is factory configured at 208Vac, 60 Hz input and output.

Without transformer, Input and Output of the UPS must always be
the same.

On 11KVA, 10% de-rating for 200/208VAC. Isolated 120/208/240VAC are
available with EX RT Transformer Module.

Introduction

1 — 3

86-86000-00 B00

UPS Characteristics

MAIN 1 (Normal AC Source) default

Power

Rating

Input

Voltage

(VAC)

Input Current (A)

Input

Breaker

(A)

Output

Voltage

(VAC)

Output

Current

(A)

Inrush

Current

Min

Max

Online

Bypass

5 kVA

208

18

32

21.6

19

40

208

19.25

200A/1ms

7 kVA

25

45

30.3

26.65

50

23.5

11 kVA

38

64

44

42

70

47.5

Transformer Module Characteristics

Input Voltage (VAC)

208/240

Output Voltage (VAC)

120/120

208

240

Max. Output Current (A)

33.3/33.3

52

45