Installation and User Manual

2.9

Connection of Optional CLA Module

1.

Connect the battery power cable

and battery detection cable

(provided with the CLA Module)

between the Power Module and the CLA Module.

2.

Connect the DC Input of the CLA Module to high power battery cabinet.

◗ DC Input Cable cross-section (not provided): maximum 4 AWG solid or stranded wire.

3.

Connect the utility AC input to terminal blocks L1 and L2 of the CLA.

◗ AC input cable cross-section (not provided): maximum 16 AWG solid or stranded wires.

Field wiring connections to terminal block shall be made using the following:

– No. 14 AWG, 60º C copper wires for AC inputs.

– No. 10 AWG, 75º C copper wires for DC inputs.

Figure 2-17: Rear view of CLA Module cable battery and AC input connections

42

40

Installation

2 — 19

86-86000-00 B00

DC Input to

High Power

Battery Cabinet

Separate, 15A Utility

AC Source

@ 208 or 240

Use 15A DBL. Pole CB

42

40

Connection Diagram
(inside CLA Module)

- +

DC INPUT

240Vdc

N L

(L2) (L1)

AC INPUT

156-280Vac

Terminal tightening torque:
– 5 lb-in. for AC input terminals
– 18 lb-in. for DC input terminals