Installation and user manual – MGE UPS Systems EX-7 User Manual

Page 49

Advertising
background image

Installation and User Manual

Table 3-1: Local Settings.

Display

Factory setting

Options

Language

English

French, Spanish, German, Italian

Date/time format

International

US

Date/time change

(DD-MM-YYYY/HH:MM)

MM-DD-YYYY/HH:MM adjustable

Audible alarm

Quick beeps

Slow beeps

Table 3-2: Output Features.

Display

Factory setting

Options

Comments

Output voltage

208 Volts AC (***)

200/208/220/230/240/250

Input voltage must be equal to
output voltage

Frequency converter

Disabled

Enabled

Bypass AC source disabled

Output frequency

Auto ranging

50/60 Hz

User selectable under
frequency converter mode

ECO mode

Disabled

Enabled

See section 3.4.2.

Hot standby

Disabled

Enabled

Full redundancy (see Figure 3-3)

Operating mode

Industrial

IT Network

(*) See Table 3-5.

Bypass

When bypass NOK

When bypass OK (**)

(*) See Table 3-5.

Transfer

Interrupt time

10 ms

10 to 200 ms

Interrupt time calibration during

(by steps of 10 ms)

during load transfer when
Bypass AC source
is out of tolerances

Overload level

102%

50/70%

(*) : - Select "IT Network" for computer loads. Select “Industrial” for other applications or when there exists and absolute need
for service continuity (with potential 10msec. interrupt) when Bypass AC source is not within set tolerances.
See table 3-5 for more details

(**) UPS will switch to Bypass AC Source if it is within the set tolerances.

(***) Input voltage must be equal to output voltage.

Figure 3-3: Configuration used to provide cascade redundancy to critical loads.

Operation

3 — 3

86-86000-00 B00

Utility

AC Source

NORMAL AC

LOAD

BYPASS AC

NORMAL AC

Protective Device

Protective Device

Cascade redundancy configuration
offers better protection to critical
load, whereas the first UPS acts as
the Bypass AC Source for the
second UPS.