EX 5/7/11RT Systems

1.5.3

Multiple Battery Module Backup Time at Full Load

Standard EX 5/7/11RT systems (one Power Module, and one Battery Module), offers a standard backup time of 5
to 12 minutes at full load.

To increase backup time, it is possible to connect up to 5 additional Battery Modules to the standard system. See
section 2.8 for connections between standard system and Battery Module (EXB 5/7/11RT)

Figure 1-9: Typical back-up time with multiple EXB’s at full load.

See Appendix for additional Back-up time information.

1.5.4

Battery Extension Cable Kit

(6 ft./1.8 m, Part number 86006)

This extended battery cable kit will be used instead of the standard battery cable when Battery Modules (EXBs) are
distant from each other (located in two different enclosures, for instance).

The battery extension cable kit includes a 6 ft. long, straight connector battery power cable and a 6 ft. long battery
detection cable.

Introduction

+

+

+

7 kVA :

11 kVA:

7 min

5 min

20 min

14 min

32 min

22 min

+

+

45 min

30 min

57 min

42 min

72 min

53 min

Standard

EX 5/7/11RT systems

Optional

Configurations

5 kVA :

9 min

25 min

45 min

60 min

84 min

100 min

EX 5/7/11RT EXB 5/7/11RT

EXB 5/7/11RT

EXB 5/7/11RT

EXB 5/7/11RT

EXB 5/7/11RT

EXB 5/7/11RT