Installation and user manual – MGE UPS Systems EX-7 User Manual

Page 39

Advertising
background image

Installation and User Manual

2.7

System Connections

WARNING

This type of connections must be carried out by qualified electrical personnel.

Before carrying out any connections, check that battery circuit breaker

is

OFF and that the upstream protection devices (Normal and Bypass AC

sources) are open (OFF/OPEN).

2.7.1

Connections with Common Normal and Bypass AC Sources (Single Mains)

Figure 2-11: Power Module I/O Box Terminal Block Diagram.

NOTE

The Power Module is factory configured for single input, whereas both Normal AC

and Bypass AC sources are identical, by means of jumper between L1 and L3.

Jumper must be removed for separate Normal AC and Bypass AC sources

(2 Mains) or with Frequency Converter application.

Keep Manual Bypass Switch

at Normal position.

7

14

Installation

2 — 13

86-86000-00 B00

L6 L5 L2 L1 L1 L4 L3

Jumper

(see note)

Output

200/208/220/230/240Vac

Normal AC source

200/208/220/230/240Vac

Bypass AC source

200/208/220/230/240Vac

Terminal block capacity:
- Max. 4AWG (EX 11RT)
- Max. 6AWG (EX 5/7RT)

Terminal tightening torque:
– 18 lb-in. for EX 5/7RT Power Module
– 35 lb-in. for EX 11RT Power Module