EX 5/7/11RT Systems

1 — 12

86-86000-00 B00

1.5.8

CLA Charger Module

Extended back-up time (up to 8 hours at full load) requires a high power battery cabinet connected to the EX
5/7/11RT via the CLA Module.

IMPORTANT

The CLA can not be used to charge the Battery Module (EXB). It is designed to
charge the customer provided high power battery cabinet.

Figure 1-12: CLA Module Contents and Connections.

Table 1-7: Battery backup time chart.

Total battery voltage : 240 VDC (20 x 12VDC, one string).

IMPORTANT

The battery capacity must be set within the UPS (5 Ah increment)
See UPS Personalization section 3.2.

Battery Backup Time

Recommended Batteries

EX 5RT

EX 7RT

EX 11RT

2 hours

50 Ah

65 Ah

100 Ah

4 hours

100 Ah

130 Ah

200 Ah

8 hours

200 Ah

260 Ah

400 Ah


EX 5/7/11RT

~

50A

(cable not included)

Typical High Power
Battery Cabinet

(not included)

15A Utility

AC Source

(cable not included)

(see section 2.10 for cable

connection information)