Power module i/o box, Ex 5/7/11rt systems – MGE UPS Systems EX-7 User Manual

Page 40

Advertising
background image

Proceed as follows:

1.

For normal AC input, make connections to L1, L2 and terminals only. No connections are required for

Bypass AC input. Make connections to , L5, L6 terminals for output.

CAUTION:

Always connect the earth ground wire first.

Jumper must be between L1 and L3. System is factory configured for 208VAC
output.

2.

Attach I/O Box to the Power Module with three screws.

Figure 2-12: Normal AC Input and Output Cables installation.

EX 5/7/11RT Systems

Installation

2 — 14

86-86000-00 B00

Card Settings

RS232 Download

66074

UPS

data

Reset

100 10

1 2

ON

ETHERNET

IP=

MAC=00E0D8FF855E

1

2

OFF

O

OFF

O

Output to Load

or

Transformer Module

(if applicable)

AC INPUT

UPSTREAM
CIRCUIT
BREAKER

(NOT SUPPLIED)

To Load or
Transformer Module
(if applicable)

Normal AC

Simplified Connection Diagram

Normal AC Input

Output

L6 L5 L2 L1 L1 L4 L3

Jumper

Output

200/208/220/230/240Vac

Normal AC source

200/208/220/230/240Vac

Bypass AC source

200/208/220/230/240Vac

To Load

208VAC

From Utility

208 VAC

Power Module I/O Box

Bypass AC