Battery module power module, Installation and user manual – MGE UPS Systems EX-7 User Manual

Page 61

Advertising
background image

Installation and User Manual

4.4

Hot Swapping the Battery Module

During the replacement of the Battery Module, it is imperative to use the same type and number of element as the
original Battery Module provided with the UPS to maintain an identical level of performance and safety. In case of
doubt, don’t hesitate to contact our Customer Care Center for more information, or refer to our web site at
www.mgeups.com.

Figure 4-3: Rear view of the Battery Module.

Maintenance

4 — 5

86-86000-00 B00

4.4.1

Disconnecting the Battery Module

1.

Switch the battery circuit breaker(s)

to

the OFF position.

2.

Disconnect the cables

and

from the

Power Module.

The Battery Module can be replaced.

The connected equipment is powered by the UPS,

but not protected.

It is also possible to replace the battery packs

instead of Battery Module.

CAUTION:

Always replace both
battery packs with
new ones.

To remove battery pack:

1.

First, switch the battery circuit breaker(s) to

the OFF position.

See section 2.4.2 and follow instructions for

battery pack replacement.

4.4.2

Re-connecting the Battery Module

1.

Reconnect the battery cables

and

to

the Power Module.

2.

Switch the battery circuit breaker(s)

to the

ON position.

14

42

40

42

40

14

42

40

14

Battery Module

Power Module