Maintenance

4.0

Scope

Maintenance includes a troubleshooting guide of symptoms and possible solutions, hot swapping the Power Module
and Battery Module, and testing scenarios.

4.1

Troubleshooting

If any of LEDs

or

is on, there is an operating anomaly or an alarm.

Use "scroll up" or "scroll down" function button to reset the audible alarm.

Table 4-1: Troubleshooting not requiring MGE after-sales support.

Symptoms

Indication

Correction

LED

is on, and Bypass AC

AC source is not connected

Rewire correctly to the Normal AC

source is present

to the correct terminals.

source.

the LCD display shows
BAD CONNECTION
REWIRE AC NORMAL

LED

is on,

Load supplied by Bypass AC source.

Push the ON button for more than 3

the LCD display shows:

seconds.

LOAD LEVEL
XX kW / XX KVA

LED

is on, and Bypass AC

UPS overload

Check if any device is shorted or

source is present

failed.

the LCD display shows:
THERMAL OVERLOAD
1XX%

LED

is on, the LCD

Short circuit conditions on output

Check if any load has shorted or

display shows:

devices.

failed.

CURRENT OVERLOAD

LED

is on,

180° degree phase shift between

Check if Bypass source is correctly

but the LCD display shows:

bypass and normal AC source.

wired

BYPASS REVERSE

(in case of upstream transformer use).

REWIRE BYPASS

Audible alarm is on,

Input/Output box not

Check if the Input/Output box

the LCD display shows:

installed correctly.

is correctly installed. See section 2.7.

I/O BOX REMOVED

Check for correct I/O Box.

15

18

17

17

17

18

17

4 — 1

86-86000-00 B00