Installation and user manual – MGE UPS Systems EX-7 User Manual

Page 59

Advertising
background image

Installation and User Manual

4.2

Hot Swapping the Power Module

This operation can be performed without interrupting the load.

Figure 4-1: Disconnecting the Power Module.

Maintenance

4 — 3

86-86000-00 B00

1.

Stop the system with the OFF button

(press more than 3 seconds). System is now

powered by Bypass AC source.

Check if UPS is on Bypass AC source by

verifying that:

LED

is ON (If LED

is not ON, do not

turn the manual bypass and call the after sales

support department).

2.

Turn the manual bypass switch

to the

BYPASS position.

3.

Switch the battery circuit breaker(s)

to the

OFF position.

CAUTION: Do not switch the Normal AC

source circuit-breaker

to

the OFF position.

Doing so will disconnect

power to the load.

4.

Loosen three screws to remove the
Input/Output box.

5.

Disconnect the battery cables

and

from the Power Module.

The Power Module can be replaced.

The connected equipment is powered by the

Bypass AC source.