2.7.3

Connections with Separate Normal and Bypass AC sources (2 Mains)

CAUTION:

This connection requires isolation Transformer Module. Call MGE

Technical Support for details.

Figure 2-14: Normal AC and Bypass AC inputs, Output Cables Installation, and Simplified Connection Diagram.

EX 5/7/11RT Systems

Installation

2 — 16

86-86000-00 B00

4

Card Settings

RS232 Download

66074

UPS

data

Reset

100 10

1 2

ON

ETHERNET

IP=

MAC=00E0D8FF855E

1

3

Output

Bypass

Normal

OFF

O

OFF

O

OFF

O

To Load or

Transformer Module

(if applicable)

2

L3

L1

MAINS 2

BYPASS AC

NORMAL AC

MAINS 1

LOAD

With separate Normal and Bypass AC inputs, supplied by separate sources.

Isolation

Transformer

(PN 86211)

Proceed as follows:

1.

Remove the cover plate under the I/O Box. Loosen the
terminal blocks L1 and L3, and remove the jumper.

CAUTION:

Always connect the earth ground wire
first.

2.

Install Normal AC, Bypass AC and output cables as shown.

3.

Reinstall the cover plate under the I/O Box with four screws.

4.

Secure the I/O Box to the Power Module with three screws.

See section 2.7.2 for connecting EX RT Transformer
module, if applicable.