Ex 5/7/11rt systems – MGE UPS Systems EX-7 User Manual

Page 64

Advertising
background image

EX 5/7/11RT Systems

5 — 2

86-86000-00 B00

5.3

System Backup Characteristics

Table 5-2: Backup Time (in minutes).

11 kVA with 9Ah battery modules:

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

Standard

90 40

25

18

14

11 9 7 6 5

Std + 1 EXB

191

93

61

43

30

24

20

17

15

14

Std + 2 EXB

293

143

96

71

53

44

34

27

24

22

Std + 3 EXB

392

199

135

99

84

60

51

43

35

30

Std + 4 EXB

525

261

172

120

102

86

67

56

48

42

Std + 5 EXB

637

312

201

142

113

102

87

68

60

53

7 kVA with 7Ah battery modules:

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

Standard

121

57

37

28

21

15

12

10

8

7

Std + 1 EXB

266

125

80

61

53

37

30

24

22

20

Std + 2 EXB

447

203

124

101

83

66

55

45

38

32

Std + 3 EXB

578

244

185

128

108

90

75

61

53

45

Std + 4 EXB

756

364

245

169

132

110

98

77

69

57

Std + 5 EXB

889

453

287

232

164

133

118

102

86

72

5 kVA (US model only) with 7Ah battery modules:

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

Standard

170

91

49

33

25

21

16

13

11

9

Std + 1 EXB

358

170

110

84

60

46

39

31

27

25

Std + 2 EXB

540

260

170

120

100

75

64

57

52

45

Std + 3 EXB

740

355

240

170

122

110

95

84

68

60

Std + 4 EXB

892

505

290

235

170

135

119

105

92

84

Std + 5 EXB

1220

540

355

260

225

170

140

120

110

100

5.4

System Short Circuit Protection

Short circuit current provided by EX 5/7/11RT in normal or battery mode:

EX 5/7RT

110A for 80ms

EX 11RT

150A for 80ms

5.5

Accessories Electrical Characteristics

EX RT Transformer Module

Nominal power

11 kVA

Nominal current

63 A

Input voltage

208-240Vac

Output Voltage

120/208/240Vac

Frequency

50/60 Hz (+/-10%)

Isolation (EN 61558-1-2-4)

3.75 kV / 5 M ohms

Operating temperature

From 0° to +40°C

Max. operating rel. humidity

95%

Derating/altitude

Pn-10% > 1000 m

EX RT CLA Module

AC input voltage

156-280 Volts AC

Input frequency

40-70 Hz

Battery charge current

6 A DC