2.7.2

Connecting EX RT Transformer Module

(Part number 86211)

This module is to provide isolated 120/208/240 VAC outputs to the protected loads.

Figure 2-13: View of EX RT Transformer Module connected downstream for 120/208/240 Vac outputs (shown

with one EXB).

Installation and User Manual

Installation

2 — 15

86-86000-00 B00

POWER MODULE
EX 5/7/11 RT

TRANSFORMER
MODULE EX RT

AC NORMAL

INPUT

TRANSFORMER MODULE

OUTPUT TO LOAD

Terminal Block Transformer Module Connection diagram
(located on bottom of Transformer I/O Box)

L3

L2

L1

Lb

Ld N

Lc La

208Vac

240Vac

AC Input

120Vac

208Vac

AC Output

120Vac

240Vac

Terminal Block capability :
AWG 4 solid or stranded wire.

BATTERY MODULE

EXB 5/7/11 RT

AC INPUT

UPSTREAM
CIRCUIT
BREAKER

(NOT SUPPLIED)

Transformer Module

Bypass AC

Normal AC

Simplified Connection Diagram

To Load

WARNING

To avoid overloading transformer windings, provide branch over current

protection for all transformer output terminals.

To avoid overloading 120VAC output windings, distribute loads evenly

between Load 2 and Load 4 (on rear of Transformer Module ) and between

120VAC output terminals (Lb-N, La-N.)

AC Input from

Power Module

(208VAC shown)

AC Output to Load

(120VAC shown)

L3 L2 L1

Lb Ld N Lc La

Transformer Module I/O Box