Power module i/o box, Installation and user manual – MGE UPS Systems EX-7 User Manual

Page 43

Advertising
background image

Installation and User Manual

2.7.4

System Connections as Frequency Converter (without Bypass AC source)

Figure 2-15: Accessing Terminal Blocks for Input and Output power cables.

Installation

2 — 17

86-86000-00 B00

Card Settings

RS232 Download

66074

UP

S

data

Res

e

t

100

10

1 2

ON

ETHER

NET

IP

=

MAC=00E0D8FF855E

1

2

OFF

O

OFF

O

Output to Load

or

Transformer Module

(if applicable)

Normal AC Input

Output

L6 L5 L2 L1 L1 L4 L3

Jumper

Output

200/208/220/230/240Vac

Normal AC source

200/208/220/230/240Vac

Bypass AC source

200/208/220/230/240Vac

OUTPUT

To Load

208VAC

INPUT

From Utility

208 VAC

Power Module I/O Box

1

OFF

O

CAUTION: Always connect the

earth ground wire first.

1.

Remove the cover plate under the I/O Box.

Remove the jumper connecting L3 and L1.

CAUTION: Removing the jumper will

disable the Bypass AC
source. Do not connect
anything to the Bypass AC
terminal block.

2.

Refer to section 2.7.1 to install Normal AC source
and output wires per I/O Box Terminal diagram.
Re-install the cover plate under the I/O Box.

3.

Secure the I/O Box to Power Module with three
screws.

See section 2.7.2 for connecting EX RT
Transformer Module, if necessary.