Device Addressing and Message Routing

31007492

19

2.1.2

Routing to Host Based Network Adapters

For host based network adapters, the byte following the adapter's

network node address specifies a task number (1 ... 8) to which the

message is assigned. Subsequent bytes are not checked by the adapter,

and are available for custom use to the application - for example, for

message counts or status information.

2.1.3

Routing to BM85 Bridge/Multiplexers

Routing to Serial Ports on BM85 Programmable Models

For the programmable models, the user application stored in the BM85

defines the addressing between Modbus Plus and the serial ports.

Routing to a Single Slave Device on BM85 Modbus Models

For a single slave device at a Modbus port, two bytes are used to address

the device. The next-to-last non-zero byte addresses the BM85 node

(1 ... 64). The last non-zero byte specifies the Modbus port (1 ... 4), and

therefore specifies the single slave device.

Figure 5 shows an example of routing to a single slave device.

BP85

ADDRESS

(1 ... 64)

BM85

ADDRESS

(1 ... 64)

BM85

PORT

(1 ... 4)

ZERO

ZERO

Figure 5

Modbus Plus Routing to Single Modbus Slave

Routing to a Networked Slave Device on BM85 Modbus Models

For a slave device on a Modbus network at a Modbus port, three bytes

are used to address the device. The third byte from the last non-zero

byte addresses the BM85 node (1 ... 64). The next-to-last non-zero

byte specifies the Modbus port (1 ... 4). The last non-zero byte specifies

the Modbus address of the slave device (1 ... 247).

Figure 6 shows an example of routing to a networked slave device.

BP85

ADDRESS

(1 ... 64)

BM85

ADDRESS

(1 ... 64)

BM85

PORT

(1 ... 4)

ZERO

SLAVE

ADDRESS

(1 ... 247)

Figure 6

Modbus Plus Routing to Networked Modbus Slave