Schneider Electric Modbus Plus Network Bridge Multiplexer none User Manual

Page 43

Advertising
background image

Configuring the Modbus Models

31007492

33

Timeout Examples

Here are some examples for setting the link timeout value. Each is

based on a Modbus message transaction of 256 bytes to the port device

and 256 bytes from the device.

V Parameters: RTU, 9600 baud, 1 start, 8 data, no parity, 1 stop.

Serial communication time: (10Ăbits)/9600 = 1.04 ms/character,

267 ms for 256 bytes (RTU mode sends one character per byte).

Slave controller scan time: 100 ms.

BM85 time: 4 ms.

Total time: (267Ă+Ă267Ă+Ă100Ă+Ă4) = 638 ms.

Use a link timeout value of 10 (1000 ms).

V Parameters: ASCII, 9600 baud, 1 start, 8 data, 1 parity, 1 stop.

Serial communication time: (11Ăbits)/9600 = 1.15 ms/character,

294 msĂxĂ2 = 588 ms for 256 bytes (2 chars/byte for ASCII).

Slave controller scan time: 100 ms.

BM85 time: 4 ms.

Total time: (588Ă+Ă588Ă+Ă100Ă+Ă4) = 1280 ms.

Use a link timeout value of 15 (1500 ms).

V Parameters: ASCII, 300 baud, 1 start, 8 data, 1 parity, 2 stop.

Serial communication time: (12Ăbits)/300 = 40 ms/character,

10.24 secondsĂxĂ2 = 20.48 s for 256 bytes (2 chars/byte for ASCII).

Slave controller scan time: 100 ms.

BM85 time: 4 ms.

Total time: (20.48 sĂ+Ă20.48 sĂ+Ă100ĂmsĂ+Ă4Ăms) = 41.06 s.

Use a link timeout value of 450 (45000 ms, or 45 s).