background image

Configuring the Modbus Models

31007492

44

3.7 Your Configuration Screens

You have four configuration screens:

V1

Use this screen to display and set the communication parameters for

each port.

V2

Use this screen to display and set locations 1 ... 32 of the Modbus

Address Map table for each port.

V3

Use this screen to display and set locations 33 ... 64 of the Modbus

Address Map table for each port.

V4

Use this screen to Save or Initialize the BM85 configuration.

Help Screens: V5, V6, V7, V8

You have four Help screens that you can access during configuration.

You can select the Help screens by selecting screens V5, V6, V7, or V8.

Pressing the `question mark` ( ? ) key will display Help for the

configuration screen you are currently using.

3.7.1

Entering Commands Into Your Screens

When the BM85 is initially powered up for configuration, the V1 screen

is shown for port 1. You can begin entering the port 1 parameters

immediately.

The currently active port is always shown at the bottom line of your

screen.

To select another screen for the active port, enter commands V1, V2, V3,

or V4. To select another port, enter commands P1, P2, P3, or P4.

When you enter the configuration commands, you can enter them singly

or as a string. Press ENTER to complete the entry. To correct

keystrokes in an entry, press DELETE. To cancel an entry before

completing it, press ESCAPE.