Configuring the Programmable Models

31007492

58

4.1 Before You Start

4.1.1

Models Covered in This Chapter

This chapter covers the configuration process for the following models:

Part Number

Mounting
Method

Operating
Power
(Nominal)

Modbus Plus
Network
Cable

Serial
Ports

Serial
Protocol

NW–BM85E232

Panel or Shelf

115/230 Vac or
24 Vdc

Single or Dual

RS232

Programmable,
User Defined

NW–BM85D002

19 in Rack

125 Vdc or
24 Vdc

Single or Dual

RS232

Programmable,
User Defined

NW–BM85E485

Panel or Shelf

115/230 Vac or
24 Vdc

Single or Dual

RS485

Programmable,
User Defined

NW–BM85S232

Panel or Shelf

115/230 Vac or
24 Vdc

Single or Dual

RS232

Programmable,
User Defined

NW–BM85S485

Panel or Shelf

115/230 Vac or
24 Vdc

Single or Dual

RS485

Programmable,
User Defined

4.1.2

An Overview of the Configuration Process

The BM85 requires an internal program for controlling its operation,

with parameters for each serial port you will use in your application.

The unit contains a nonĆvolatile memory that stores your program and

port configurations, even when operating power is removed.

You must create your BM85 application program and download it across

the Modbus Plus network to the BM85. A switch is provided on the

BM85 to enable the unit to accept the download. If the unit is already

installed at its site and connected to the network, you can download your

program to it. You can also download your program at a spare network

connection near your download host, then transport the configured

BM85 to the site and install it.

Caution:ąYou must complete the internal configuration of the

BM85 before making the unit active in your application, both

on the Modbus Plus network and at its serial ports.

If you are installing a BM85 that was previously configured for

another application, another network, or different node, the

unit will still be retaining its previous configuration setup.

You must not connect the unit into the current application and

apply operating power to the unit until you have reconfigured

it for the current application.