Configuring the Modbus Models

31007492

40

3.5 Configuring the Modbus Ports

3.5.1 Connecting Power for the Configuration

3.5.2 Setting the Switches

1 2 3 4 5 6 7 8

SWITCH POSITION

1 2 3 4 5 6 7 8

PORT MODE:

CONFIGURE

RUN

CONFIGURATION PORT:

PORT 1

PORT 2

PORT 3

PORT 4

PARITY:
DISABLED

EVEN

DISABLED

ODD

BAUD RATE:
9600

2400

1200

300

UP

UP

UP

DOWN

DOWN

DOWN

UP

UP

DOWN

DOWN

UP = 1 DOWN = 2

NW-BM85-000
(Pv02 or earlier)

NW-BM85C002

NW-BM85D008
NW-BM85-000
(PV03 or greater)

USE

UPPER

SWITCHES

USE

RIGHT

SWITCHES

NW-BM85-000 = ST OP BITS:

UP = RUN APPLICATION

NW-BM85C002

rEFENW-BM85D008 = MODE:

(LEAVE IN UP POSITION)

UP

UP

DOWN

DOWN

UP

UP

DOWN

DOWN

UP

UP

DOWN

DOWN

UP

UP

DOWN

DOWN

Figure 10 BM85 Modbus Models: Port Configuration Switches

Refer to the installation chapter in this guide for connecting power to

your BM85. Connect the source of AC or DC power to the BM85. Do

not turn on the power to the BM85 until you set the Modbus port

configuration switches and connect the configuration terminal. The

switch settings will be sensed when power is applied.

The BM85 power should be set off at this time. Switches are located on the

BM85 rear panel. Figure 10 shows the switch positions and setup.