Your configuration commands, 6 your configuration commands – Schneider Electric Modbus Plus Network Bridge Multiplexer none User Manual

Page 52

Advertising
background image

Configuring the Modbus Models

31007492

42

3.6 Your Configuration Commands

EachĂscreenĂshowsĂtheĂcommands that are valid for that screen. You can

use either upper or lower case when entering a command.

Command

Action

Range

V

Select a configuration screen or Help screen

1 ... 8

P

Select a port to be configured

1 ... 4

N

Enter a Modbus slave device address

1 ... 247

T

Enter the port type

M = Master
S = Slave
N = Network
X = Silent Master Network

B

Enter the baud rate

50, 300, 1200, 1800, 2000, 2400,
3600, 4800, 7200, 9600, 19200

S

Enter the stop bits

1 or 2 (Note 1)

R

Enter the parity mode

N = None
O = Odd
E = Even

M

Enter the communication mode

A = ASCII
R = RTU

Y

Enter the port priority

1 ... 4

L

Enter the link timeout value

1 ... 3000, in multiples of 100 ms

F

Enter the modem booster selection

Y = Yes
N = No

W

Write the configuration parameters to all four ports

D

Initialize all four ports with default parameters

?

Display Help for the current configuration screen

E

Enter a Modbus address and five–byte routing path into
the Modbus Address Map table on the V2 or V3 screen.

When you use this command, enter the following:

– the E command
– the table location (1 ... 64) for your entry
– the Modbus address (1 ... 255) to be mapped
– the five bytes of routing (1 ... 255 in each byte).

Entry format:
EYY MM XX XX XX XX XX

where:

E = Modbus Address Map command
YY = location (1 ... 64) in the table
MM = Modbus address (1 ... 255)
XX = each byte (1 ... 255) in the path.

Notes

1. Models NW-BM85C002 and NW-BM85D008 do not have a

Stop Bits setting. These models default to 8 data bits with 1 Stop Bit.

Advertising