Configuring the Modbus Models

31007492

32

3.4.6

Link Timeout

The Purpose of the Parameter

Link timeout is the maximum time you will allow for a slave device to

respond to a command issued at the BM85 Modbus slave port. In your

application, if the timeout value is exceeded, a `slave device down` error

code will be returned by the program function initiating the command to

the device.

If the timeout value is too short, slower devices may not have time to

respond normally to their commands, resulting in apparent errors at the

device. If the value is too long, and a device fails to respond, your

application will have to wait until the timeout occurs before handling the

device condition or using the port again.

A value should be set to handle the slowest device at the port, without

excessive delay. The value should accommodate the sum of the

following:

V serial communication time

V slave device processing time: for example, controller scan time

V BM85 processing time for port transactions, approximately 4 ms.

Setting the Parameter

You set each port's timeout parameter as a value in the range 1 ... 3000.

The timeout value represents multiples of 100 milliseconds.

For example, a parameter of 10 specifies a link timeout of 10 x 100 ms,

or one second.