Modbus port indicator codes, 13 modbus port indicator codes – Schneider Electric Modbus Plus Network Bridge Multiplexer none User Manual

Page 64

Advertising
background image

Configuring the Modbus Models

31007492

54

3.13 Modbus Port Indicator Codes

If the BM85 detects a condition that prevents communication at its

Modbus Plus or Modbus ports, it shuts off all ports and displays an error

code pattern at its four Modbus port indicators.

Indicator layouts are shown in Figure 22.

The error pattern produces two 4-bit codes for two hexadecimal digits.

First, the indicators show a steady pattern for one second, indicating the

upper digit. Then they show a flashing pattern for one second with the

lower digit. The continuous and flashing patterns alternate repetitively.

Port 4 is the most significant bit in each code.

Indicators

Pattern

Hexadecimal Digit

4 – 3 – 2 – 1

Steady

Upper digit

4 – 3 – 2 – 1

Flashing

Lower digit

Hardware Error Codes: 11 ... 19 Hex

Code (Hexadecimal)

Meaning

11

PROM checksum error

12

RAM data test error

13

RAM address test error

14

Normal power down event

17

Bad or unexpected interrupt

18

EEPROM checksum error

19

Modbus port loopback error

Modbus Driver Error Codes: 24 ... 2E Hex

Code (Hexadecimal)

Meaning

24

Modbus transmit state error

25

Modbus receive state error

26

ASCII transmit communications state error

27

Transmit underflow error

28

RTU transmit communications state error

29

ASCII receive communications state error

2A

RTU receive communications state error

2B

Transmit communications state error

2C

Receive communications state error

Advertising