Device Addressing and Message Routing

31007492

20

2.2 Modbus Address Conversion

Programmable Port Models

For the programmable models, the user application stored in the BM85

defines the addressing conventions to be used between the serial ports

and Modbus Plus. The application program must define the routing

between serial ports, as well as the paths to Modbus Plus nodes.

Modbus Port Models

For the Modbus port models, address conversion between Modbus and

Modbus Plus addresses is provided internally as described below.

Examples are shown in Section 2.3.

When the BM85 receives a message at a Modbus port, the Modbus

address (1 ... 255) is compared to an internal address map for that port.

You define the map table during your BM85 configuration. It can hold

up to 64 Modbus addresses, each pointing to a five-byte routing path.

If an address match is found in the table, the five routing path bytes are

applied to the message. If the first byte is in the range 1 ... 64, the

message is routed out on Modbus Plus. If the first byte is zero, the

message goes to a Modbus port (1 ... 4) specified in byte two. If that port

has a single slave device, the remaining three bytes are zeros. If the port

has a network of slave devices, byte three specifies the slave address.

RESERVED

RESERVED

0

1

64

65

79

80

255

DIRECT

ATTACH

ADDRESS

MUX ATTACH

ADDRESS

IMPLICIT

ATTACH

ADDRESS

70

71

74

75

RESERVED

NOTE:

ALL ADDRESSES 65 ... 79
ARE RESERVED AT ANY
PORT CONFIGURED IN THE
‘SILENT MASTER’ MODE.

Figure 7

Bridge Multiplexer Address Conversion