Silent Master Port Considerations

In the Silent Master port configuration, one Modbus master device and

one or more Modbus slave devices can be connected as a Modbus

network at the port. This allows the master device to address the slave

devices directly, as well as to address other devices at other ports on the

same BM85 or across Modbus Plus.

In the Silent Master configuration, the slave devices on the port must

have unique addresses in your application. They must not be the same

as a node address (1 ... 64) on the BM85's local Modbus Plus network.

They must also not exist as entries in the Modbus Address Map table

that you setup within the BM85.

The Modbus addresses in the master's queries to the slave devices at the

Silent Master port must not map beyond the port -- not to any routing

path on Modbus Plus, nor to another port on the BM85.