Modbus Plus Port Status Indicators

The green MODBUS PLUS indicator shows the overall communication

status at the BM85 node. Two red indicators for ERROR CHANNEL A

and ERROR CHANNEL B identify errors on the two Modbus Plus cable

paths.

If the ERROR CHANNEL A or ERROR CHANNEL B indicator blinks

momentarily, it indicates that a message error was detected on the

Modbus Plus cable path. A steady ON state indicates a hard fault exists,

either in the cable or in a node device connected to it. If communication

is lost on one cable path, the other path continues normally.

The MODBUS PLUS indicator flashes repetitive patterns to show the

BM85 node's communication status on the Modbus Plus network. The

patterns are:

Six Flashes per Second

This is the BM85 node's normal operating state. All nodes on the

network should be flashing this pattern. If the indicator is OFF

continuously, the BM85 is not transmitting on the network.

One Flash per Second

The BM85 node is offline after just being powered up, or after hearing a

message from another node with the same network address (duplicate

addresses are not allowed). In this state, the node monitors the network

and builds a table of active nodes. It remains in this state for five

seconds, then attempts to go to its normal operating state.

Two Flashes, then OFF for Two Seconds

The BM85 node is hearing the token being passed among other nodes,

but is never receiving the token. Check the network link for an open or

short circuit, or defective termination.

Three Flashes, then OFF for 1.7 Seconds

The BM85 node is not hearing any other nodes. It is claiming the token,

but finding no other node to which to pass it. Check the network link

for an open or short circuit, or defective termination.

Four Flashes, then OFF for 1.4 Seconds

The BM85 node has heard a valid message from another node that is

using the same address as this node. The BM85 node remains offline in

this state as long as it continues to hear the duplicate address. If the

duplicate address is not heard for five seconds, the node then changes to

the pattern of one flash every second.