Schneider Electric Modbus Plus Network Bridge Multiplexer none User Manual

Page 59

Advertising
background image

Configuring the Modbus Models

31007492

49

31007492

3.9.2

Using the V2 or V3 Screen

Use the V2 screen for configuring entries 1 ... 32 for the selected port.

Use the V3 screen for configuring entries 33 ... 64 for this port.

You can alternate between the V2 and V3 screens using commands V2

and V3.

The Table Entry column is a listing of locations in the table. Note that

these are table entry locations, not Modbus addresses. You must enter

the Modbus addresses that you want to map into the second column.

When you edit the table entries, you do not have to do so in a defined

sequence. For example, you do not have to configure E1 before

configuring another entry.

You do not have to fill all the table entries in the V2 screen before

making an entry in the V3 screen. If you will use no more than 32

entries, you might find it convenient to keep them all on one screen.

Example

To use the V2 screen table entry E1 to map Modbus address 20 to the

routing path 21 22 23 24 25, you would enter the following string:

E1 20 21 22 23 24 25 <ENTER>

You may find it convenient to use a Modbus addressing convention that

helps you to remember how addresses are mapped in your application.

For example, you can use the Modbus address 124 to define mapping to a

Modbus Plus node address 4, with routing through a Bridge Plus at

address 20. In the same convention, Modbus address 126 would map to

Modbus Plus node 6 through the same bridge. Examples are shown in

table entries E4 and E6.

To map the addresses shown at E4 and E6, you would enter the

following strings:

E4 124 20 4 0 0 0 <ENTER>

E6 126 20 6 0 0 0 <ENTER>

Advertising