Configuring the Modbus Models

31007492

26

3.1 Before You Start

3.1.1

Models Covered in This Chapter

This chapter covers the configuration process for the following models:

Part Number

Mounting
Method

Operating
Power
(Nominal)

Modbus Plus
Network
Cable

Serial
Ports

Serial
Protocol

NW–BM85–000

Panel or Shelf

115/230 Vac

Single

Modbus

ASCII or RTU

NW–BM85C002

Panel or Shelf

115/230 Vac or
24 Vdc

Single or Dual

Modbus

ASCII or RTU

NW–BM85D008

19 in Rack

125 Vdc or
24 Vdc

Single or Dual

Modbus

ASCII or RTU

3.1.2

An Overview of the Configuration Process

The BM85 requires the setup of internal configuration parameters for

each port that you will use in your application. The unit contains a

nonĆvolatile memory that stores the port configurations, even when

operating power is removed.

You must set the port configurations using a serial terminal (or a PC

with a terminal emulation program) connected to one of the BM85 ports.

The BM85 does not have to be connected to the Modbus Plus network.

A switch is provided on the BM85 to enable the unit to be configured.

If the unit is already installed at its site, you can configure it there.

You can also do the configuration prior to installing the unit at its site,

then transport the configured unit to the site and install it.

You must also set the Modbus Plus node address into a set of switches on

the BM85 rear panel.

Caution:ąYou must complete the internal configuration of the

BM85 before making the unit active in your application, both

on the Modbus Plus network and at its serial ports.

If you are installing a BM85 that was previously configured for

another application, another network, or a different node, the

unit will still be retaining its previous configuration setup.

You must not connect the unit into the current application and

apply operating power to the unit until you have reconfigured

it for the current application.