UPS Model and Battery Configurations

This UPS is designed to work with single-phase, three-wire, AC power
sources. There are two important considerations when selecting the UPS
model and battery configuration to properly safeguard your equipment:
S Load requirements
S Battery times

Load Requirements

The load is the equipment to be protected by the UPS. Select the UPS
model that meets the power consumption requirements of the load in
volt-amperes (VA). The total load VA should not exceed the UPS VA
rating. To determine the total load requirements:

1. Obtain the load ratings from either the nameplate or operator’s

manual of the equipment to be protected by the UPS. The
ratings are listed in either watts (W), amperes or amperes
max (A), or volt-amperes.

2. If the rating is in watts, multiply by 1.4 to obtain the VA

requirement (this is the typical relationship between watts and
volt-ampere ratings in most computing equipment). However,
in some new computing equipment, the power supply is
power-factor corrected and the watts rating equals the VA
requirement. Check with the manufacturer to determine
applicability.

If the rating is in amperes or amperes max, multiply by the
input voltage to obtain the VA requirement.