Powerware 6000 User Manual

Page 55

Advertising
background image

Installation

47

Powerware

®

9 Prestige Series User’s Guide (4500/6000 VA)

S

Rev H

www.powerware.com

UPS with PPDM Startup

To start up the UPS:

1. Verify the PPDM input breaker is in the OFF (O) position (see

Figure 13 on page 39).

2. Confirm the correct UPS output voltage is selected (see Step 4

on page 41).

3. Turn on the equipment that is connected to the UPS.

4. Confirm the Bypass switch on the PPDM rear panel is in the

NORMAL position (see Figure 13 on page 39).

5. If your PPDM is a hardwired unit, supply utility power to the

UPS and skip to Step 8.

6. If your PPDM is a plug/receptacle unit, plug the input power

supply cord into the utility input receptacle on the PPDM rear
panel.

7. Plug the other end of the power supply cord into a grounded,

three-wire, AC receptacle that has been wired in accordance
with NEC specifications or national wiring rules. See Chapter 6,
“Specifications” on page 69 for the input current/output voltage
requirements.

8. Switch the circuit breaker to the ON (

|

) position (see

Figure 14 on page 40) on each battery cabinet connected to the
PPU.

Each battery cabinet performs a self-test and then enters normal
operation. The battery cabinet startup should take about three
seconds.

9. For plug/receptacle units, verify that the circuit protectors for

output receptacles are in the ON position (pushed in).

10. Switch the PPU input breaker to the ON (

|

) position (see

Figure 14 on page 40).

11. Switch the PPDM input breaker to the ON (

|

) position (see

Figure 13 on page 39).

The UPS performs diagnostic tests and enters Normal mode
with the equipment (load) offline. The

µ

indicator remains

lit. The startup should take about 15 seconds.

Advertising
This manual is related to the following products: