Powerware 6000 User Manual

Page 37

Advertising
background image

Installation

29

Powerware

®

9 Prestige Series User’s Guide (4500/6000 VA)

S

Rev H

www.powerware.com

Mounting Holes

Plug/Receptacle
PPU Connector

Three Foot Cord

Terminal Block

Access Hole
for Conduit

Figure 6. Optional REPO Cord Junction Box

Optional REPO Cord Junction Box Connections

Wire Function

Terminal

Position

Terminal Wire Size

Rating

Suggested Wire

Size

REPO

L1

TB1-4

L2

TB1-5

12 - 22 AWG

(4 - 0 mm

2

)

18 AWG (0.75 mm

2

)

Ground

TB1-6

(4 - 0 mm

2

)

(

)

N

N

N

NO

O

O

OT

T

T

TE

E

E

E

The REPO function activates when L1 and L2 are shorted together.

UPS Hardwired Installation

W A R N I N G

Only qualified service personnel (such as a licensed electrician) should perform the
hardwired installation.

Use the following procedure to install the PPU and battery cabinets:

1. Place the UPS near the equipment to be protected. The UPS

should be well ventilated and away from direct sunlight or
other heat source.

Place the PPU underneath or beside the battery cabinets as
shown in Figure 7.

NOTE Do not connect more than six standard battery cabinets to the PPU. For
extended battery run times, contact your local distributor for additional battery
cabinets. Do not place more than six cabinets in one stack (the PPU is equal to two
cabinets).