UPS Operation

57

Powerware

®

9 Prestige Series User’s Guide (4500/6000 VA)

S

Rev H

www.powerware.com

Voltage
Selector
Switch

Figure 25. Voltage Selector Switch

4. Plug the input and output cords of the PPDM into the power

connectors on the PPU as shown in Figure 24 on page 55.

5. Switch the PPU input breaker to the ON (

|

) position.

After a short delay (approximately three seconds), the UPS
front panel indicators turn on and cycle through several times.
The

µ

and

indicators remain lit for several seconds (UPS

in Bypass mode).

6. Press and hold the Output On button until you hear the UPS

beep (approximately one second).

The

µ

indicator remains lit and the Self Test indicator turns

on.

7. Turn the Bypass switch on the PPDM to the NORMAL position.

The front panel displays the percentage of full load being
applied to the UPS. The UPS is now in Normal mode with the
load online.