Communications Mode Reference Chart

The following chart defines the UPS serial port contacts. Serial
communication is not available with 3Com and AS/400 network
configurations. Use only the applicable pins for the selected
communication mode; otherwise, interference problems may occur.

Communication Mode Function

Signal Name Pin No.

True Condition

Serial

Data to UPS

RS232 TxD

2

N/A

Data from UPS

RS232 RxD

3

N/A

Signal Ground

7

Novell
(D f l )

Battery On

ON.AC

14/16

Open

(Default)

Low Battery

TWO.MIN

23/24

Closed

Signal Ground

7/15/25

Novell
(C

)

Battery On

ON.AC

14/16

Closed

(Custom)

Low Battery

TWO.MIN

23/24

Closed

Signal Ground

7/15/25

3Com
(D f l )

Shutdown (Remote)

SHUT.DOWN

2

Positive Voltage

(Default)

Low Battery

LOW.BATT

9

Positive Voltage

Battery On

PWR.FAIL

10

Positive Voltage

Signal Ground

7

AS/400

UPS Available

UPS Available

11/13

Closed

Battery On

Utility Failure

14/16

Closed

Bypass

UPS Offline

17/19

Closed

Low Battery

Low Battery

23/24

Closed

Signal Ground

12/15/18/25

N

N

N

NO

O

O

OT

T

T

TE

E

E

E

Pin numbers separated by a forward slash ( / ) are connected together internally.