Using the PPDM

The PPDM provides continuous online power for your equipment. With
the PPDM, you can replace or upgrade the PPU without losing power to
your equipment. Figure 23 shows the operation of the UPS with the
PPDM.

PPU

In

Out

Battery

Battery

Utility
Power

PPDM

UPS Load

Figure 23. UPS and PPDM Block Diagram

Using Maintenance Bypass

Use the following procedure to transfer the critical load to Maintenance
Bypass (AC Line operation) and remove the PPU:

1. Turn the Bypass switch on the PPDM to the BYPASS position

(see Figure 24). The PPDM is now powering your equipment
from utility power.

2. Press and hold the Output

Off button until the long beep

ceases (approximately three seconds). The

µ

indicator

remains lit.

3. Switch the PPU input breaker to the OFF (O) position.

The UPS enters Battery mode for several seconds. The

µ

indicator turns off and the UPS shuts down.